Description
E7 200Smart CPU Standard Edition,CPU SR20 Relay,12DI/8DO,1*RJ45,2*RS485, Expandable to 6IO
CPU SR20 AC/DC/RLY Specifications
Model No: SR20 AC/DC/RLY
Article No: E7 288-1SR20-0AA1
Description: Standard CPU SR20, Relay
Conventional Norm: Not specified
Dimensions (WxHxD): 90 × 100 × 81 mm
Power Consumption: 14W
Available Current (SM Bus): Max. 1400mA
Available Current (24V DC): Max. 300mA
CPU Features
- Program Memory: 12 KB
- Data Memory: 8 KB
- Retentive Memory: 10 KB
- Data Preservation: Permanent
- Built-in I/O: 12 Digital Inputs / 8 Digital Outputs
- Process Image Size: 256-bit Input (I) / 256-bit Output (Q)
- Analog Image: 56 words Input (AI) / 56 words Output (AQ)
- Expansion Modules Allowed: Up to 6 modules
- High-Speed Counters (Total): 6 total (4 @ 200KHz + 2 @ 30KHz)
- Pulse Output: None
- Timer: 192 Non-Holding (TON, TOF), 64 Holding
- Counters: 256
- Bit Memory (M): 256 bits
- Cycle Interrupt: 2 total, T32 and T96 (1ms resolution)
- Interrupt Edge: 4 Up and 4 Down
- Real-Time Clock: 7 days (at 25°C, minimum 6 days)
- Memory Card: Supported
- Signal Expansion Board: Supported
Performance/Processing Time:
- Boolean: 0.35 µs/instruction
- Moving Word Operations: 1.2 µs/instruction
- Floating Point: 1.7 µs/instruction
Communications Built-in
- Ports:
- Ethernet: 1
- Serial Ports: 2 (DB9-RS485)
- DB Board Serial Port: 1 (CM01-RS485-RS232)
- HMI Connections:
- Ethernet: 8 connections
- Serial Port: 4 connections
- Programming (PG): 1 connection
- Ethernet (CPU PUT/GET): 8 clients and 8 servers connections
- Open Type Communication: 8 active and 8 passive connections
- Data Transmission Rate:
- Ethernet: 10/100 Mb/s
- RS485 System Protocol: 9600, 19200, 187500 b/s
- RS485 Free Port: 1200 to 115200 b/s
- Isolation:
- Ethernet: 1500VDC Transformer isolation
- RS485: None
- Cable Type:
- Ethernet: CAT5e Shielded cable
- RS485: PROFIBUS Network cable
Power
- Input Voltage: 85-264VDC
- Input Current (CPU Only):
- 130mA at 120V AC (without 300mA sensor supply)
- 250mA at 120V AC (with 300mA sensor supply)
- 80mA at 240V AC (without 300mA sensor supply)
- 150mA at 240V AC (with 300mA sensor supply)
- Inrush Current (Max): 9.3A at 264VDC
- Sensor Voltage: 20.4-28.8VDC
- Isolation:
- Input to Logic: 1500VAC, 1 minute
- Sensor to Logic: Not isolated
Digital Input
- Number of Inputs: 12
- Input Type: Sinking / Sourcing type (IEC type 1 sinking)
- Allowable Continuous Voltage: Max. 30VDC
- Surge Voltage (Max): 35V DC for 0.5s
- Logic 1 Signal (Min): 15V DC (2.5mA current)
- Logic 0 Signal (Max): 5V DC (1mA current)
- Optical Isolation: 500V AC for 1 minute (field side and logic side)
- Filter Time: Each channel can be separately selected (0.2 µs, 0.4 µs, 0.8 µs, 1.6 µs, 3.2 µs, 6.4 µs, 12.8 µs; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms, 12.8 ms)
Digital Output
- Number of Outputs: 8
- Output Type: Relay, dry contact
- Voltage Range: 5-30VDC or 5-250VAC
- Surge Current (Max): 7A when power on
- Rated Current per Point (Max): 2.0A
- Switching Frequency (Max): Not recommended
- Turn-on Delay: Up to 10ms (Qa.0 to Qa.3)
- Turn-off Delay: Up to 10ms (Qa.4 to Qa.7)
- Optical Isolation: 500V AC for 1 minute (field side and logic side)
- Contact Lifetime:
- Non-loaded: 10,000,000 cycles
- Rated Load: 10,000 cycles
This text should give a comprehensive view of the specifications for the CPU SR20 AC/DC/RLY model, clearly organized in sections. Let me know if you need further information or adjustments!