Huceen

Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts.
To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

CPU ST20XP DC/DC/DC

Categories: E7 200smart CPU

Description

E7 200Smart CPU Standard Edition,CPU ST20XP Transistor,12DI/8D0/4AI/2AO,1*RJ45,2*RS485,3*100KHz high-speed pulse, Expandable to 6IO

General Overview

  • Model Number: ST20XP DC/DC/DC
  • Article Number: E7 288-1ST20-XPA1
  • Description: Standard Edition CPU with 4 inputs, 2 outputs with analog signals, and transistor outputs.
  • Dimensions (WxHxD): 110 mm × 100 mm × 81 mm
  • Power Consumption: 18W

Electrical Specifications

  • Available Current:
    • SM Bus: Max. 1400mA
    • 24V DC: Max. 300mA
  • Input Voltage: 20.4V – 28.8V DC
  • Input Current (CPU only):
    • Without 300mA sensor power supply: 190mA at 24V DC
    • With 300mA sensor power supply: 470mA at 24V DC
  • Input Current (Includes CPU + Expansion Modules):
    • At 24V DC: 680mA
  • Inrush Current (Max): 6A at 28.8V DC
  • Sensor Voltage: 20.4V – 28.8V DC
  • Isolation:
    • Input to Logic: None
    • Sensor to Logic: Not isolated

Memory and Data

  • Program Memory: 12 KB
  • Data Memory: 8 KB
  • Retentive Memory: 10 KB (permanent data preservation)
  • Bit Memory (M): 256 bits
  • Cycle Interrupts: 2 (T32 and T96) with a 1ms resolution
  • Counters: 256
  • Timers:
    • Non-retained (TON, TOF): 192 timers
    • Retained: 64 timers

I/O Specifications

  • Built-in I/O:
    • Digital Inputs: 12 (Sinking/Sourcing type, IEC type 1 sinking)
    • Digital Outputs: 8 (Solid-MOSFET, source-type)
    • Analog Inputs: 4 (Voltage/Current inputs)
    • Analog Outputs: 2 (Voltage/Current outputs)

Digital I/O Characteristics

Digital Inputs:

  • Allowable Continuous Voltage: Max. 30V DC
  • Surge Voltage (Max): 35V DC (lasting 0.5s)
  • Logic 1 Signal (Min): 15V DC at 2.5mA (for standard inputs)
  • Logic 0 Signal (Max): 5V DC at 1mA
  • Optical Isolation: 500V AC (lasting 1 minute)
  • Filter Time: Configurable for each channel (ranging from 0.2 µs to 12.8 ms)

Digital Outputs (Solid-MOSFET, Source-Type):

  • Voltage Range: 20.4V – 28.8V DC
  • Surge Current (Max): 8A (lasting 100ms)
  • Rated Current per Point (Max): 0.5A
  • Switching Frequency: Not specified (likely low-frequency operation)
  • Turn-on Delay (Qa.0-Qa.3): Max. 1.0 µs (from disconnection to connection)
  • Turn-off Delay (Qa.4-Qa.7): Max. 50 µs (from disconnection to connection)
  • Optical Isolation: 500V AC (lasting 1 minute)

Analog I/O Characteristics

Analog Inputs (4 channels):

  • Input Types: Voltage or current (can be selected as a group)
  • Input Range:
    • Current Mode: 0-20mA
    • Voltage Mode: 0-10V
  • Resolution: 12 bits (both current and voltage modes)
  • Accuracy:
    • Voltage Mode: ±0.3% to ±0.5% of full scale range
    • Current Mode: ±0.4% to ±0.6% of full scale range
  • Analog-to-Digital Switching Time: 50ms (at 50Hz)

Analog Outputs (2 channels):

  • Output Types: Voltage or current
  • Output Range:
    • Current Mode: 0-20mA
    • Voltage Mode: 0-10V
  • Resolution: 11 bits (both current and voltage modes)
  • Accuracy:
    • Typical (at 25°C): ±0.5% to ±1.0% of full scale range
    • Worst Case (0 to 55°C): ±0.5% to ±1.0% of full scale range
  • Diagnosis: Upflow/underflow; 24V DC low voltage
  • Maximum Cable Length: 100m (Shielded twisted pair)

Performance and Processing Time

  • Boolean Operations: 0.35 µs per instruction
  • Moving Word Operations: 1.2 µs per instruction
  • Floating Point Operations: 1.7 µs per instruction

Communications and Ports

  • Ethernet:
    • 1 Ethernet port (10/100 Mb/s)
    • CPU Communication (PUT/GET): 8 clients and 8 servers connections
    • Open Type Communication: 8 active and 8 passive connections
  • RS485:
    • 2 DB9-RS485 ports
    • 1 DB board serial port (CM01-RS485-RS232)
    • RS485 Free Port: Supports 1200 to 115200 b/s data transmission rates
  • HMI Connections:
    • 8 connections via Ethernet
    • 4 connections via serial port
  • Programming (PG) Connection: 1 connection

Expansion and Counters

  • Expansion Modules Allowed: Up to 6 modules
  • High-Speed Counters: 6 in total, with specific frequencies:
    • Single Phase: 4 counters at 200kHz + 2 counters at 30kHz
    • Quadrature Phase: 2 counters at 100kHz + 2 counters at 20kHz