Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts.
To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

EM AR02 Thermocouple module

Categories: Temperature Module

Description

2-channel RTD module, resolution 16 bits

Model and Article Information

  • Model Number: EM AR02
  • Article Number: E 288-3AR02-0AA1
  • Description: 2-channel RTD module with a 16-bit resolution for precise temperature measurement.

Physical and Power Specifications

  • Dimensions (WxHxD): 47 mm × 100 mm × 81 mm
  • Power Consumption: 1.5 W
  • Current Consumption:
    • SM bus: 120 mA
    • 24V DC: 40 mA

Analog Input Specifications

  • Number of Inputs: 2
  • Measuring Principle: Sigma-Delta (high-precision conversion method)
  • Resolution:
    • Temperature: 0.1°C / 0.1°F
    • Voltage: 15 bits + symbol bits (providing high precision for voltage measurements)
  • Max. Voltage Resistance: ±35V (ensuring protection against voltage spikes)
  • Max Power Consumption of Sensor: 0.5 mW

Isolation and Protection

  • Isolation:
    • Field side and logic side: 500V AC
    • Field side and 24V DC side: 500V AC
    • 24V DC side and logic side: 500V AC
    • Channel to channel isolation: None specified (common grounding for channels)
  • Common Mode Rejection: >120 dB (excellent at rejecting noise from common-mode sources)
  • Repeatability: ±0.05% FS (Full Scale)

Cable and Sensor Specifications

  • Cable Loop Resistance (Max):
    • 20Ω for standard RTD (Cu10), with a maximum of 2.7Ω for special configurations.
  • Cable Length: Can handle up to 100 meters with shielded twisted pair cable, ensuring accurate measurements even over long distances.

Diagnosis and Error Handling

  • Diagnosis Features:
    • Overflow/underflow detection
    • Circuit break detection
    • 24V DC low voltage warning (ensures proper system operation by notifying of power issues)

Frequency Rejection and Filter Selection

  • Rejection Frequency Selection:
    • 400 Hz (2.5 ms integration time)
    • 60 Hz (16.6 ms integration time)
    • 50 Hz (20 ms integration time)
    • 10 Hz (100 ms integration time)
  • Note:
    • When selecting the 400 Hz filter, the module maintains resolution and accuracy, while also suppressing noise at 100 Hz and 200 Hz frequencies.