Huceen

Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts.
To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

SM1223 DI16x24VDC &DQ16xRLY

Categories: Digital Module

Description

Digital input &output module DI16 x 24VDC sinking/sourcing type & DQ16x relay, relay output

Model and Article Information

  • Model Number: SM1223 DI16x24VDC & DQ16xRLY
  • Article Number: H7 223-1PL32-0XB0
  • Description: Digital input and output module featuring 16 digital inputs (sinking/sourcing type) and 16 relay outputs (dry contact).

Physical and Power Specifications

  • Dimensions (WxHxD): 70 mm × 100 mm × 75 mm
  • Power Consumption: 10 W
  • Available Current:
    • SM bus: 180 mA
    • Sensor power (24V): 4 mA per input point; 11 mA per relay coil

Digital Input Specifications

  • Number of Inputs: 16
  • Input Type: Sinking/Sourcing type (IEC type 1 sinking)
  • Surge Voltage: 35 V DC (lasting 0.5 s)
  • Logic 1 Signal (Min): 15 V DC at 2.5 mA
  • Logic 0 Signal (Max): 5 V DC at 1 mA
  • Optical Isolation: 500 V AC, lasting 1 min (between field side and logic side)
  • Isolation Groups: 2 groups
  • Filter Time Options: 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms, and 12.8 ms (selectable; 4 inputs form one group)

Digital Output Specifications

  • Number of Outputs: 16
  • Output Type: Relay (dry contact)
  • Voltage Range:
    • DC: 5-30 V DC
    • AC: 5-250 V AC
  • Maximum Electric Current: 2 A per output
  • Lamp Load:
    • DC: 30 W
    • AC: 200 W
  • Flood Leakage Current of Each Point: Not specified
  • Surge Current: 7 A when the contact is closed
  • Isolation:
    • Coil and Contact Side: 1500 V AC (lasting 1 min)
    • Coil and Logic Side: None (no isolation between coil and logic side)
  • Isolation Groups: 4 groups
  • Current of Each Public Terminal (Max): 8 A
  • Switching Delay: Up to 10 ms
  • Mechanical Lifetime (non-responsible): 10,000,000 open/close cycles
  • Lifetime under Rated Load: 100,000 open/close cycles
  • Behavior at RUN-STOP:
    • Previous value or replacement value (default is 0)