Huceen

Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts.
To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

SM1223  DI16x24VDC &DQ16x24VDC

SM1223 DI16x24VDC &DQ16x24VDC

Categories: Digital Module

Description

General Information

  • Model No: SM1223 DI16x24VDC & DQ16x24VDC
  • Article No: H7 223-1BL32-0XB0
  • Description:
    • This module has 16 digital inputs and 16 digital outputs.
    • Input Type: Sinking/ sourcing.
    • Output Type: Transistor output (solid-state MOSFET).

Dimensions

  • Width: 70 mm
  • Height: 100 mm
  • Depth: 75 mm

Power Consumption

  • Total Power Consumption: 4.5W
  • Available Current (SM Bus): 185 mA
  • Available Current (Sensor Power 24V): 4 mA per input point used

Digital Input

  • Number of Inputs: 16
  • Input Type: Sinking / Sourcing
  • Surge Voltage: 35 VDC (lasting for 0.5s)
  • Logic 1 Signal (Min): 15 V DC at 2.5 mA
  • Logic 0 Signal (Max): 5 V DC at 1 mA
  • Optical Isolation (Field Side and Logic Side): 500 V AC, lasting for 1 minute
  • Isolation Group: 2
  • Filter Time Options:
    • 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms (optional; four inputs form one group)

Digital Output

  • Number of Outputs: 16
  • Output Type: Solid-MOSFET (Source type)
  • Voltage Range: 20.4 - 28.8 V DC
  • Logic 1 Signal (Min): 20 V DC (at maximum current)
  • Logic 0 Signal with 10KΩ Load (Max): 0.1 V DC
  • Electric Current (Max): 0.5 A
  • Lamp Load: 5 W
  • Flood Leakage Current of Each Point (Max): 10 μA
  • Surge Current: 8 A (lasting for 100 ms max)
  • Isolation (Field Side and Logic Side): 500 V AC, lasting for 1 minute
  • Isolation Group: 1
  • Current of Each Public Terminal (Max): 8 A
  • Switching Delay:
    • From disconnection to connection (Max): 50 µs
    • From connection to disconnection (Max): 200 µs

Mechanical Lifetime

  • Non-Responsible Lifetime: Not specified
  • Lifetime Under Rated Load: Not specified

Behavior at RUN-STOP

  • Upon running and stopping, the module’s behavior will depend on the configuration:
    • Default Behavior: Replacement value is 0, or the previous value can be retained.