Huceen

Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts.
To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

SM1223  DI8x24VDC &DQ8x24VDC

SM1223 DI8x24VDC &DQ8x24VDC

Categories: Digital Module

Description

Model: SM1223 DI8x24VDC & DQ8x24VDC

Article Number: H7 223-1BH32-0XB0

Description:

  • Type: Digital input and output module.
  • Inputs: 8 digital inputs (sinking/sourcing type, 24VDC).
  • Outputs: 8 transistor (solid-state MOSFET) outputs, 24VDC.

General Specifications:

  • Dimensions (WxHxD): 45 × 100 × 75 mm
  • Power Consumption: 2.5W
  • Current Consumption (SM Bus): 145mA
  • Sensor Power (24V): 4mA per input point.

Digital Input Specifications:

  • Number of Inputs: 8
  • Input Type: Sinking/Sourcing type (digital inputs)
  • Surge Voltage: 35VDC, lasting 0.5s
  • Logic 1 (Min): 15V DC at 2.5mA
  • Logic 0 (Max): 5V DC at 1mA
  • Optical Isolation: 500V AC, lasting 1 minute (field side and logic side)
  • Isolation Group: 2
  • Filter Time: Configurable (0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms) with inputs grouped in sets of 4.

Digital Output Specifications:

  • Number of Outputs: 8
  • Output Type: Solid-state MOSFET (source type, N-channel transistor).
  • Voltage Range: 20.4 - 28.8V DC
  • Logic 1 Signal at Maximum Current: Minimum 20V DC
  • Logic 0 Signal (with 10kΩ Load): Maximum 0.1V DC
  • Maximum Electric Current: 0.5A per output.
  • Lamp Load: 5W
  • Flood Leakage Current per Point: Maximum 10μA
  • Surge Current: Maximum 8A, lasting up to 100ms
  • Isolation: 500V AC, lasting 1 minute (field side and logic side)
  • Isolation Group: 1
  • Current per Common Terminal (Max): 4A
  • Switching Delay:
    • From disconnection to connection (Max): 50µs
    • From connection to disconnection (Max): 200µs
  • Mechanical Lifetime (non-responsible): Not specified
  • Lifetime Under Rated Load: Not specified
  • Behavior at RUN-STOP: Either previous value or replacement value (default is 0).