Omron

Kindly browse your automation parts that you are looking for on this page! MISEL does offer automation parts from other brands as well such as SIKO, WAGO, AUTONICS, FUJI, and many more. In addition, we also offer support services such as product introduction, installation to our customers who purchase automation parts. To get further details especially about price and availability status of products, don’t be hesitate to contact our marketing team. We are always available to assist you to get your automation needs. Thank You!

Description

Temperature Controller Selection Guide

E5Z Series Digital Controllers:

Item Model

E5CZ E5EZ E5AZ E5EZ-PRR

Appearance

Omron E5CZ

Omron E5EZ Omron E5AZ Omron E5EZ-PRR

No. of loops

1

Size

48 × 48 mm (front mount)

48 × 96 mm (front mount)

96 × 96 mm (front mount)

48 × 96 mm (front mount)

Input accuracy

±0.5%

Input type

Thermocouple K, J, L, T, E, U, N, R, S or B; RTD Pt-100, JPt-100; Infrared temperature sensor;

Voltage input: 0 to 50 mV

Input impedance

Current input: 150 Ω, Voltage input: 1 MΩ

Sampling rate

250 ms

Power supply

Universal AC Power (100 to 240 VAC, 50/60 Hz), 24 VAC, 50/60 Hz or 24 VDC

Universal AC Power (100 to 240 VAC, 50/60 Hz)

Operating power

85% to 110% of rated supply voltage

Power consumption

100 to 240 VAC: 7.5 VA max. 24 VAC: 5.5 VA max. 24 VDC: 3.5 W max.

100 to 240 VAC: 8.5 VA max. 24 VAC: 6 VA max. 24 VDC: 4 W max. 10 VA (10W)

Control type

ON/OFF or 2 PID control (with auto-tuning)

2 PID control (with autotuning)

Control mode

Heating/cooling control

Position proportional control only

Control output

Relay output: SPST; SSR driver (voltage); Current output

Relay output: 2 nos of relays (SPST), for open and close function

Auxiliary output

Not supported

Event output

2 max.

Logic operation

Not supported

Transfer output

Not supported

Remote setpoint

Not supported

Potentiometer

Not supported

100 to 2500 Ω

Heater / SSR failure detection

Heater detection (1 CT only)

Not supported

Setting method

Digital setting using front panel key or software access

Indication method

11-segment 2-line digital and individual indicator

7-segment 3-line digital and single lighting indicator

Setpoint program

Not supported

Bank switching

Not supported

Communication type

RS-485 communication type, supporting Compoway/F or Modbus

RS-232 or RS-485 communication type, supporting Compoway/F or Modbus

Alarm

2 alarms 3 alarms 2 alarms

Configuration software

USB-Serial conversion cable with Thermo Mini software