• Semi-multi power supply voltage.
• Large transparent time setting knob facilitates time setting.
A flat-blade and Phillips screwdriver can also be used for time setting.
• Pin configuration compatible with MY Power Relay.
• LED indication for power and output statuses.
• Conforms to EMC standards.
• Conforms to EN 61812-1 and approved by UL and CSA.
Specification
Time Ranges
Rated time | Time setting range | Rated time | Time setting range |
---|---|---|---|
0.5 s | 0.04 to 0.5 s | 3 min | 0.1 to 3 min |
1 s | 0.1 to 1 s | 5 min | 0.2 to 5 min |
5 s | 0.2 to 5 s | 10 min | 0.5 to 10 min |
10 s | 0.5 to 10 s | 30 min | 1 to 30 min |
30 s | 1.0 to 30 s | 60 min | 2 to 60 min |
60 s | 2.0 to 60 s | 3 h | 0.1 to 3 h |
120 s | 5.0 to 120 s | — | — |
Ratings
Item | H3Y-2(-0)/H3Y-4(-0) |
---|---|
Rated supply voltage *6 *7 |
100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz), 24 VAC (50/60 Hz) *1 12, 24, 48, 125, 100 to 110 VDC *2, *3 |
Operating voltage range | All rated voltages except 12 VDC: 85% to 110% of rated supply voltage 12 VDC: 90% to 110% of rated supply voltage *4 |
Reset voltage | 10% min. of rated supply voltage *5 |
Power consumption | 100 to 120 VAC: 1.5 VA (at 120 VAC) 200 to 230 VAC: 1.8 VA (at 230 VAC) 24 VAC: 1.5 VA (at 24 VAC) 12 VDC: 0.9 W (at 12 VDC) 24 VDC: 0.9 W (at 24 VDC) 48 VDC: 1.0 W (at 48 VDC) 100 to 110 VDC: 1.3 W (at 110 VDC) 125 VDC: 1.3 W (at 125 VDC) |
Control outputs | H3Y-2(-0): 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load is 1 mA at 5 VDC (P reference value). Contact materials: Ag H3Y-4(-0): 3 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load is 1 mA at 1 VDC (P reference value). Contact materials: Au-clad + Ag-alloy |
Ambient operating temperature | -10°C to 50°C (with no icing) |
Storage temperature | -25°C to 65°C |
Ambient operating humidity | 35% to 85% |
*1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Timers for details on your OMRON website.
*2. With DC ratings, single-phase full-wave rectified power sources may be used.
*3. Only the H3Y-2 and H3Y-2-0 Series include 12 VDC models.
*4. Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously
under an ambient operating temperature of 50°C.
*5. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC:10 VAC max.
200 to 230 VAC:20 VAC max.
100 to 110 VDC:10 VDC max.
*6.Refer to Safety Precautions for All Timers on your OMRON website when combining the Timer with an AC 2-wire proximity sensor.
*7. A diode to prevent reverse voltages is provided only on models with a DC power supply.
Characteristics
Accuracy of operating time | ±1% FS max. (0.5 s range: ±1%±10 ms max.) *1 |
---|---|
Setting error | ±10%±50 ms FS max. |
Reset time | Min. power-opening time: 0.1 s max. (including halfway reset) |
Influence of voltage | ±2% FS max. *1 |
Influence of temperature | ±2% FS max. *1 |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts) *2 2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) *2 2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) *2 1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Impulse withstand voltage | Between power terminals: 3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC 1 kV for 12 VDC, 24 VDC, 48 VDC Between exposed non-current-carrying metal parts: 4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC 1.5 kV for 12 VDC, 24 VDC, 48 VDC |
Noise immunity | ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
Static immunity | Destruction: 8 kV Malfunction: 4 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75-mm single amplitude Malfunction: 10 to 55 Hz, 0.5-mm single amplitude |
Shock resistance | Destruction: 1,000 m/s2 (approx. 100G) *3 Malfunction: 100 m/s2 (approx. 10G) |
Life expectancy | Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h) Electrical: H3Y-2: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h) H3Y-4: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h) *4 |
Enclosure rating | IP40 |
Weight | Approx. 50 g |
EMC | (EMI) EN 61812-1 Emission Enclosure: EN 55011 Group 1 class A Emission AC Mains: EN 55011 Group 1 class A (EMS) EN 61812-1 Immunity ESD: IEC 61000-4-2 Immunity RF-interference: IEC 61000-4-3 Immunity Burst: IEC 61000-4-4 Immunity Surge: IEC 61000-4-5 Immunity Conducted Disturbance: IEC 61000-4-6 Immunity Voltage Dip/Interruption: IEC 61000-4-11 |
Approved standards | UL 508, CSA C22.2 No. 14, Lloyds, CCC: GB/T 14048.5 *6 Conforms to EN 61812-1 and IEC 60664-1. (2.5 kV/2 for H3Y-2/-2-0, 2.5 kV/1 for H3Y-4/ -4-0) *5 |
*1. Add ±10 mS to the above value for the 0.5-S range model.
*2. Terminal screw sections are excluded.
*3. The destructive shock resistance test was performed on the Timer.
*4. Check the electrical life curve.
*5. Overvoltage category II.
*6. CCC certification requirements
Model | H3Y-2 (-0) | H3Y-4 (-0) |
---|---|---|
Recommended fuse | RT14-20/6A (380 VAC 6 A), manufactured by DELIXI |
RT14-20/4A (380 VAC 4 A), manufactured by DELIXI |
Rated operating voltage Ue Rated operating current Ie |
AC-15: Ue: 250 VAC, Ie: 3 A AC-13: Ue: 250 VAC, Ie: 5 A DC-13: Ue: 30 VDC, Ie: 0.5 A |
AC-15: Ue: 250 VAC, Ie: 2 A AC-13: Ue: 250 VAC, Ie: 3 A DC-13: Ue: 30 VDC, Ie: 0.5 A |
Rated insulation voltage | 250 V | |
Rated impulse withstand voltage (altitude: 2,000 m max.) |
2.5 kV (at 240 VAC) | |
Conditional short-circuit current | 1000 A |
For over 25 years, PT. Mitrainti Sejahtera Eletrindo (MISEL) has developed automation system solutions to assist our customers in achieving high efficiency and effectiveness in their manufacturing process. We become a trusted partner for local and global companies in diverse industries such as consumer products, tobacco industry, packaging companies, foods and beverages, pharmaceutical, industrial manufacturing, etc. With adequate experiences in automation industry, we are your first and best choice to support your automation needs.
Feel free to contact us for more information :
Sales & Marketing
Ruko Pengampon Square Blok D-31
Jl. Semut Baru, Kel. Bongkaran, Kec. Pabean Cantian Kota Surabaya – Jawa Timur
[email protected]
WhatsApp: +628170006907
T. (031) 355 1715
F. (031) 355 3995
Reviews
There are no reviews yet.